CoatingPassport · schema v1.1Demo · Power pylon

DEMO-PYLON-T-4218 — Coating Passport

Annual drone inspection of a 420 kV HV suspension tower (commissioned 1978, 60 m height). Cross-arm galvanizing loss at 68% with active red-rust; lower main-leg L-3 section loss at 12%. Conductor-attachment bird-nest noted for line-maintenance crew. Foreign-object findings demonstrate the broad coverage.

Asset

Asset ID
DEMO-PYLON-T-4218
Type
Power pylon
Material
galvanized_steel
Operator
Demo TSO

Inspection

Timestamp
Wed, 22 Apr 2026 13:00:00 GMT
Footage source
drone
Duration
20 min
Frames analyzed
36,000
Operator tier
enterprise_user
Model version
hullproof-vlm-v2.1.3

Findings summary (3)

0
critical
1
severe
1
moderate
1
minor

Findings detail

coating breakdown

confidence 91%312 framesimg-quality 85%severe

Hot-dip galvanizing loss estimated 68% across cross-arm north members. Active red rust visible — base steel exposed.

Location: Cross-arm 1, north side, members M14-M22 (0, 0, 22)
Recommended action: Schedule on-tower zinc-rich-paint touch-up within 12 months. If progression continues, plan tower-level re-galvanization at next outage window.

corrosion

confidence 83%198 framesimg-quality 79%moderate

Section loss estimated 12% on lower main leg L-3 below galvanizing breakdown zone. Within IEC 60652 + Statnett-spesifikasjon monitoring threshold.

Location: Main leg L-3, lower section (0, 0, 14)
Recommended action: Trend at next annual inspection; coordinate UT measurement at next planned line outage.

foreign object

confidence 74%12 framesimg-quality 68%minor

Bird nest fragment lodged at conductor attachment. No structural concern; flagged for line-maintenance crew awareness.

Location: Cross-arm 1, conductor attachment (1, 0, 25)
Recommended action: Removal at next planned outage.

Compliance

EU AI Act class
high_risk_ai_system
Review workflow
Pending

Applicable standards

  • IEC 60652 (Loading tests on overhead line structures)
  • EN 50341 (Overhead electrical lines exceeding AC 1 kV)
  • IEEE 691 (Guide for transmission structure foundation design)
  • NACE SP0198 (Control of corrosion under thermal insulation and fireproofing materials)
  • Statnett Tekniske spesifikasjoner — luftledninger

Interoperability

Cognite CDF compatible
Yes
OSDU mapping
Veracity export
Not exported
Knowledge graph
Not generated

The same JSON powers Cognite CDF Asset+Timeseries, OSDU exports, RDF knowledge graphs, and MCP-tool calls from agentic systems. PDF is a renderer of this; never the source.

Demo passport generated from fixtures/passports/demo-power-pylon-001.ts. Production passports are built by the analysis pipeline via buildCoatingPassport() and validated against the Zod schema at src/lib/passport/types.ts.