coating breakdown
Hot-dip galvanizing loss estimated 68% across cross-arm north members. Active red rust visible — base steel exposed.
Annual drone inspection of a 420 kV HV suspension tower (commissioned 1978, 60 m height). Cross-arm galvanizing loss at 68% with active red-rust; lower main-leg L-3 section loss at 12%. Conductor-attachment bird-nest noted for line-maintenance crew. Foreign-object findings demonstrate the broad coverage.
Axes
Indicative commercial signal
Insurance premium multiplier
×1.3 – ×1.84
Annual fuel penalty (ISO 19030)
— (no performance value)
Top drivers — every point traces to a finding or metric
Every point of `index` traces to a finding_id or SHM metric in `drivers`; recompute the same passport to reproduce. Indicative only — Hullproof sets no premium and takes no risk; this is the signal a market prices against.
Measured = read from a sensor / instrument / file header. Estimated = derived from a proxy. Modeled = AI / algorithm output. Declared = operator-supplied. Nothing is presented as stronger than its provenance.
Hot-dip galvanizing loss estimated 68% across cross-arm north members. Active red rust visible — base steel exposed.
Section loss estimated 12% on lower main leg L-3 below galvanizing breakdown zone. Within IEC 60652 + Statnett-spesifikasjon monitoring threshold.
Bird nest fragment lodged at conductor attachment. No structural concern; flagged for line-maintenance crew awareness.